Cable Chambers
Find out the GFA treatment for cable chambers
Cable Chambers Integrated with the Main Building
Cable chambers integrated within the main building are excluded from GFA if it does not exceed 2.5m in height1.

Cable Chambers Integrated Within Main Building
1 The structural beams shall also be included in the height computation.
Standalone Cable Chambers
Standalone cable chambers that fulfil either criteria below are excluded from GFA:
The height2 of the cable chamber, measured from the floor to the underside of the upper floor shall not exceed 2.0m; or
The combined height2 (a + b) shall not exceed 4.5m for Residential developments, 5.0m for Commercial developments or 6.0m for Industrial or Warehouse developments.

Example of Standalone Cable Chamber Excluded from GFA

Example of Standalone Cable Chamber Excluded from GFA
2 The structural beams shall also be included in the height computation.